Secutron Inc. 57
8.4 NAC Auto-silence, Strobe Programming (Section 2)
Please see 6.3.3 NAC Automatic Signal Silence and NAC2 Strobe Mode Programming on
page 45.
* = Factory default
8.5 Silence Inhibit and Walk Test Programming (Section 3)
Please see 6.3.4 Signal Silence Inhibit Timer and Walk Test Programming on page 46.
* = Factory default
8.6 Waterflow Programming (Section 4)
Please see 6.3.5 Waterflow Alarms Programming on page 47.
* = Factory default
ZONE
ALARM
LED On
Programming Section Settings
1 NAC Auto-silence
Enabled
*Disabled
2 NAC2 Strobe or Bell
Strobe
*Bell
ZONE
ALARM
LED On
Programming Section Settings
1 Signal Silence Inhibit Timer
Enabled
*Disabled
2 One Man Walk Test
*Audible
Silent
ZONE
ALARM
LED On
Programming Section Settings
1 Waterflow Delay Timer
Enabled
*Disabled
2 Silencing of Waterflow Alarms
*Enabled
Disabled