3.9.1.2 Special Keys During Power-on
Some keys have a special functionality when being pressed during the power-on /
boot process.
»↵« during power-on – After a con󰊟rmation dialog, the DiggiMEC enters a special
“Service Mode”. This operating mode allows for installing a new 󰊟rmware on the
DiggiMEC.
»Reset« during power-on – After a con󰊟rmation dialog, the WIC1 enters a special
“Service Mode”. This operating mode allows for installing a new 󰊟rmware on the
WIC1.
»✕« during power-on – After a con󰊟rmation dialog, the WIC1 resets all settings to
the respective factory default.
This is the same functionality as the Direct Control [Service / General] »Factory
Reset«, see ╚═▷ “2.12 Reset to Factory Defaults”.
WARNING!
As long as you are running in „Service Mode“, your equipment is protected only by the
Backup protection, not by the user settings.
This means that the Backup Protection of the WIC1, especially the WIC1‑xxxxxx1
(“Backup Protection trip as soon as possible”) variant, might output a trip pulse.
Therefore it is strictly recommended to always enter the „Service Mode“ only with the
breaker opened (or disconnected).
107WIC1WIC1-1.0-EN-MAN
3 Hardware
3.9.1.2 Special Keys During Power-on

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Seg WIC1-3 and is the answer not in the manual?

Seg WIC1-3 Specifications

General IconGeneral
BrandSeg
ModelWIC1-3
CategoryRelays
LanguageEnglish

Related product manuals