EasyManua.ls Logo

SENEC Wallbox pro s - Front Illumination; Information about Signs, Symbols and Labelling; Protective Devices; Type Plate

SENEC Wallbox pro s
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
English
26
1MΩ.Alternatively,thedifferential-current
method in combination with measuring the
PEconductorcurrentcanbeused.Avalueof
3.5mAmustnotbeexceededineithercase.
To perform these measurements, connect the
charging coupler to a test adapter for vehicle
simulation according to EN 61851-1. The meas-
urements
mustbeperformedinadapterstateC
.
The differential-current measurement must
be performed at the connection point of the
charging system’s supply cable in the building’s
electrical cabinet.
i
Depending on the measuring instrument
used, it might not be possible to perform
the following measurement on the
adapter. In this case, perform the test at
the connection terminals.
Testing the switch-off condition in the event of a
short circuit (Z
L-N
)
To perform these measurements, connect the
charging coupler to a test adapter for vehicle
simulation according to EN 61851-1. The meas-
urementsmustbeperformedinadapterstateC.
Performthemeasurementsatthetestadapter’s
measuringsockets.Thevaluesinaccordancewith
theselectedcircuitbreakermustbeobserved.
Testing the switch-off condition in the event of
the RCD tripping
To perform these measurements, connect the
charging coupler to a test adapter for vehicle
simulation according to EN 61851-1. The meas-
urementmustbeperformedinadapterstateC.
Performthemeasurementatthemeasuring
socketsofthetestadapterusingasuitable
measuring instrument. The values in accordance
withtheselectedRCDandthenetworkmustbe
observed.
Testing the integrated DC residual current
detection
To perform these measurements, connect the
charging coupler to a test adapter for vehicle
simulation according to EN 61851-1. The meas-
urementsmustbeperformedinadapterstateC.
Performthemeasurementsatthetestadapter’s
measuringsocketsusingasuitablemeasuring
instrument. The charging system must discon-
nect the charging coupler from the mains when
theresidualcurrentexceeds6mADC.Thefault
display on the charging system must respond.
1.6 Information about signs, symbols
and labelling
Hazard warning:
Information about a possibly hazardous situation
thatcouldbefatalorresultinsevereinjuriesifthe
safetymeasuresarenotobserved.Allworkistobe
performedbyskilledpersonnelonly.
Note:
Moreinformationisavailableintheoperating
instructions.
i
Note:
supplementary information.
1.7 Protective devices
The following components (Fig. XVI) are protective
devices:
1 housing, 2 charging cable, 3 protective cover,
4chargingcoupler
Checking the protective devices
» 1.Visuallyinspecttheprotectivedevicesfor
damage before every charging process.
» 2.Haveaqualiedelectricianperformthe
electrical function tests at regular intervals in
compliance with the national regulations.
1.8 Type plate, front illumination and
blocking device
1.8.1 Type plate
YoucanndthetypeplateoftheWallboxasshown
in Fig. XVI no 2.
1.8.2 Front illumination
The front illumination (Fig. XVI no. 1) indicates
the operating state of the charging system. Refer
to the operating instructions for details of the
operating states.
The charging process starts automatically as
soon as the charging coupler is inserted and the
vehicle requests the charging process.

Table of Contents