34
SENSAPHONE 400 User’s Manual
4. Enter the complete telephone number using the number keys.
The Model 400 will recite the digits as they are pressed.
4
MAX CALLS
5
TEMP LIMITS
6
CALIBRATE
8
CLOCK
3
INTERCALL
TIME
7
RECOGNITION
TIME
9
LISTEN TIME
SOUND
0
ID NUMBER
POWER
1
CALL
DELAY
2
VOICE
REPS
5. Press ENTER. The unit will respond: “Okay.
ENTER
PM
6. Repeat above procedure to program up to four separate telephone num-
bers.
STEP 4: SET TEMPERATURE LIMITS
High and low temperature limits can be separately programmed for each
zone that is configured as temperature. Limits can range from –20° to
+150°F, or from –30° to 65°C. Default settings are: 10° F for low tempera-
ture and 100° F for high temperature. Do not set temperature limits too
close to normal room temperature, since minor fluctuations could result in
frequent and unnecessary alarm dialouts.
1. Press SET.
SET
2. Press TEMP LIMITS.
5
TEMP LIMITS
3. Using the number keys, press a number (from 1 to 4) that corresponds to
the temperature zone being programmed.
4
MAX CALLS
5
TEMP LIMITS
6
CALIBRATE
8
CLOCK
3
INTERCALL
TIME
7
RECOGNITION
TIME
9
LISTEN TIME
SOUND
0
ID NUMBER
POWER
1
CALL
DELAY
2
VOICE
REPS