SENSAPHONE 400 User’s Manual
3. Press the number (1 to 4) of the selected temperature zone to be cali-
brated.
4
MAX CALLS
3
INTERCALL
TIME
1
CALL
DELAY
2
VOICE
REPS
4. Enter the number required to offset the current temperature reading so a
correct reading is obtained.
To program a positive offset number (up to +10 degrees), enter the num-
ber on the keypad. The Model 400 recites the digits as they are pressed.
To program a negative offset number (up to –10 degrees), first press *.
The unit responds with negative.Next, enter the number on the key-
pad. The unit recites the digits as they are pressed.
4
MAX CALLS
5
TEMP LIMITS
6
CALIBRATE
8
CLOCK
3
INTERCALL
TIME
7
RECOGNITION
TIME
9
LISTEN TIME
SOUND
0
ID NUMBER
POWER
1
CALL
DELAY
2
VOICE
REPS
5. Press ENTER. The Model 400 responds:“Okay.
ENTER
PM
NOTE: If you find that your calibration offset exceeds more than + 5
or –5 degrees, other complicating factors could be affecting normal
operation of the Model 400. Call Sensaphone for technical assistance.
5.6.2 InterrogatIng temperature CalIbratIon