2-2 Installation
WRMTM-40001 iPERL Water Management System Technical Manual
6. Install new system connection gaskets in both meter couplings.
7. Insert two washers into the pit setter, line the threads and tighten the bolts an extra 1/4 to 1/2
turn.
8. After the new system is installed, shut the outlet shut-off valve.
9. Open the inlet shut-off valve slowly until the system is full of water and ensure that there are
no leaks.
10. Open the outlet valve slowly until air is out of the meter and service line.
11. Open a valve downstream of the system to ensure that no foreign debris in the water obstructs
the operations of the system.
12. Check the read on the system to make sure it is registering a positive number. If it is not, make
sure the system is installed in the correct direction.
13. Attach an endpoint to the system via a coupler cable.
14. Record read information as required by the utility.
2.4 Replacing an Existing Meter
To replace an existing meter with the iPERL system:
1. Unpack the new iPERL system from the packaging.
2. Inspect the system for any parts that may have been damaged during shipping.
3. Turn off the water supply valves.
4. Pull the current meter out of the pit or disassemble current meter.
5. Orientate the new system so that the direction of the flow arrow on the system body is aligned
with the direction of the flow arrow in the plumbing system.
6. Install new system connection gaskets in both meter couplings.
Never use thin meter gaskets.
Do not over-tighten. You may tighten after turning on the water if leaks are present.
Never use thin meter gaskets.

Other manuals for Sensus iPerl

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sensus iPerl and is the answer not in the manual?

Sensus iPerl Specifications

General IconGeneral
TypeUltrasonic water meter
Measurement TechnologyUltrasonic
Protection ClassIP68
MaterialComposite
Pressure Rating232 psi (16 bar)
CommunicationAMR/AMI Compatible
Battery Life20 years
Maximum Pressure16 bar
OutputPulse
Power SupplyBattery
Temperature RangeUp to 158°F (70°C)
Operating Temperature32°F to 158°F (0°C to 70°C)