7 Service
7.1 Electronics Service by SEW‑EURODRIVE
If you are unable to rectify a fault, contact SEW‑EURODRIVE Service. For the ad-
dresses, refer to www.sew‑eurodrive.com.
When contacting the SEW‑EURODRIVE Service, always specify the following inform-
ation so that our service personnel can assist you more effectively:
• Information on the device type on the nameplate (e.g. type designation, serial
number, part number, product key, purchase order number)
• Brief description of the application
• Error message on the status display
• Nature of the fault
• Accompanying circumstances
• Unusual events preceding the problem
7.2 Extended storage
The following table shows the time intervals and maintenance works that are relevant
for extended storage of the application inverter modules.
Modules Time interval Maintenance
MDP90A...-C00/0
1)
Every 2 years
Line connections: Connect the device
to the line voltage for 5 minutes.
MDP90A....
for extended storage
above 40°C
1) Power supply module with integrated braking resistor and capacitor
For all modules other than the ones listed, no maintenance is required.
DANGER
Uncovered power connections.
Severe or fatal injuries from electric shock.
• Install the touch guards at the modules, see chapter "Touch guards"(→258).
• Install the closing covers according to the regulations, see chapter "Touch
guards"(→258).
• Never start up the application inverter without installed closed touch guards and
closing covers.