9
Functional safety
Safety Conditions
Operating Instructions – MOVIDRIVE
®
modular
255
9.3.2 Requirements on the installation
The components must be protected against conductive dirt, e.g. by installing them
in a control cabinet with degree of protection IP54 according to IEC60529.
If conductive dirt can be excluded at the installation site, a control cabinet with
lower degree of protection is permitted under observance of the applicable stand-
ards, e.g. EN60204‑1.
The same applies to temporary condensation, e.g. due to rapid changes of the am-
bient temperature.
The wiring technology used must comply with the standard EN60204-1.
The STO control cables must be routed according to EMC guidelines and as fol-
lows:
Inside an electrical installation space: Individual cores can be routed.
Adhere to the regulations in force for the application.
The sinking and sourcing cables from the external safety device to the axis
must be routed right next to each other with a cable length of ≤30m.
The sinking and sourcing cables from the external safety device to the axis
must have the same cable length. A difference in length ≤ 3% of the two cables
is permitted.
The STO control cable must be routed separately to the power lines of the
drive.
The STO function does not detect short circuits or interference voltage in the sup-
ply line. This is why you must make sure that:
No parasitic voltages can occur in the STO control cables.
or
The external safety controller can detect a crossfault from an external potential
to the STO control lines.
Observe the values specified for safety components when designing the safety cir-
cuits.
The STO signal (F_STO_P1, F_STO_P2, and F_STO_M) may not be used for
feedback.
For safety controller/safety relays, you must only use grounded voltage sources
with protective electrical separation (PELV) according to EN 61131-2 and
EN60204-1.
If several voltage sources are used, each voltage source must be connected to a
PE system.
When planning the installation, observe the technical data of the application in-
verter.
Do not use the 24-V-STO_Out of the application inverter for safety-related applica-
tions. Voltage is only permitted to supply the connection for safe disconnection X6
with plugged jumper plug.
For safety-related applications with the application inverter, the jumper plug at the
STO input X6 must be removed.
24748536/EN – 11/2017

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SEW-Eurodrive MOVIDRIVE MDA Series and is the answer not in the manual?

SEW-Eurodrive MOVIDRIVE MDA Series Specifications

General IconGeneral
BrandSEW-Eurodrive
ModelMOVIDRIVE MDA Series
CategoryControl Unit
LanguageEnglish

Related product manuals