Wiring Diagram C
Shield Fire, Safety and Security Ltd.
Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM
Revision E01.00
100 of 127
Security Ltd. Security Ltd.
NAC outputs of the Shield A-XT Releasing Fire Control
Panel are not limited by conditions other than the maximum
rated current threshold. NAC outputs of the Shield A-XT
Releasing Fire Control Panel can operate combinations of VES
authorized NAC devices as long as the circuit load does not
exceed 500 mA.
Reference manufacturer data sheets for individual device loads
and then total the loads to determine if the sum exceeds the
500 mA threshold of each NAC output.