EasyManua.ls Logo

Shield Shiel A-XT - Ground Trouble Indication; Field Wiring

Shield Shiel A-XT
137 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Specifications A
Shield Fire, Safety and Security Ltd.
Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM
Revision E01.00
69 of 127
NAC outputs on the Shield A-XT Releasing Fire Control Panel are load dependant and are limited to a maximum
current load of 500 mA. The releasing output on the Shield A-XT Releasing Fire Control Panel is load dependant
and is limited to a maximum current load of 1000 mA.
Total standby-current of these loads must draw less than 236 mA to maintain continuous standby operation for
twenty-four hours followed by five minutes of alarm.
Current loading calculations do not include the combined IDC currents of the Shield A-XT Releasing Fire Con-
trol Panel. These combined IDC currents are negligible in comparison to fire control panel, ancillary device and NAC
currents of the Shield A-XT Releasing Fire Control Panel and are therefore excluded from the current loading
calculation.
Ground Trouble Indication
A ground trouble indication occurs when a minimum of 30K Ohms exists between earth-ground and the following
VDC terminals of the fire control panel:
AUX 24V
POWER, STATUS UNITS
NAC 1, NAC 2 and NAC 3
ZONE 1, ZONE 2, ZONE 3
MODE SELECT
MAN RELEASE
•ABORT
REL. PRES. SWITCH
•EXTING.
•LOW P. SWITCH
Field Wiring
The following specifications identify the range of acceptable wire gages for field wiring, battery and power
connections:
Terminal Wire Range
AUX 24V 14 - 18 AWG
REMOTE CONTROL No Connection (NC)
DATA - STATUS UNITS
14 - 18 AWG
POWER - STATUS UNITS 14 - 18 AWG
NAC 1, NAC 2 14 - 18 AWG
ZONE 1, ZONE 2, ZONE 3 14 - 18 AWG

Table of Contents