53
Mode3 PID1 lead screen
Output 1 PID1 proportional-band (P) setting screen
Initial value : 3.0%
Setting range : OFF, 0.1 999.9%
When performing auto tuning, no necessity for a setting basically.
If OFF is chosen, it becomes ON-OFF (two positions) operation.
Output 1 PID1 Integral time (I) setting screen
Initial value : 120 seconds
Setting range : 0FF, 16000 seconds
When performing auto tuning, no necessity for a setting basically.
This screen is not displayed at the time of ON-OFF operation.
Becomes P operation or PD operation in I=OFF setting.
Output 1 PID1 Derivative time (D) setting screen
Initial value : 30 second
Setting range : 0FF, 13600 seconds
When performing auto tuning, no necessity for a setting basically.
This screen is not displayed at the time of ON-OFF operation.
Becomes P operation or PI operation in D=OFF setting.