(1) Control method
(2) Number of PID
(3) Number of Zone
(4) Zone hysteresis
(5) Proportional band (P)
(6) ON-OFF Differential gap(H)
(7) ON-OFF Differential gap(L)
(8) Integration time(I)
(9) Differential time(D)
(10) Manual reset
(11) Dead band
(12) Output limiter
(13) Soft start
(14) Control output characteristic
(15) Proportional period
(16) Output renewal period
(17) Manual output
(18) FlexPID setting method (ABC)
2mode PID method with Auto tuning +Zone PID method or ON-OFF operation
Max 8
Max 4
0~10000 units
OFF ,0.1~1000.0 FS (On – Off operation by OFF setting)
1~10000 Units
1~10000 Units
OFF ,1~6000s (P or OD operation by OFF setting)
OFF ,1~3600s (P or PI operation by OFF setting)
±50.0%(Effective at I=OFF)
-20000~30000 Units
(L) 0.0~99.9% (H)0.1~100.0% (resolution 0.1)
OFF, 0.1~300.0s (resolution 0.1)
Possible to choose from RA(Heating) or DA(Cooling)
0.5~300.0s (resolution 0.5)
Same as sampling period (50,166.7,250,500m sec)
0.0~100.0% ( resolution 0.1)
0.00~1.00
Normal open(1a) 240V AC 2A(resistance load)
12VDC -1~+1.5V (Max 20mA)
4-20mA(load resistance 500Ω ) Load regulation 0.2%FS
0-10V(Max load 2mA)
Normal open(2a) 240V AC 2A
2 circuits of Triode AC switch 240V AC 1.5A
±1.0%FS(5~100% Output)
About 1/50000