EasyManuals Logo

Shimax MAC6A User Manual

Shimax MAC6A
93 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #90 background imageLoading...
Page #90 background image
91
Program function (option
(1) Number of pattern
(2) Number of steps
(3) Time setting
(4) Time setup resolution
(5) Time accuracy
(6) Step setting parameter
(7) Step signal
(8) Pattern end signal
(9) Program END
(10) Time signal
(11) Pattern execution number:
(12) PV start
(13) Guarantee soak
(14) Hold
(15) Skip
(16) Power failure compensation
Max 8 (1, 2, 3, 4, 6, 8 patterns)
1296 (Total steps = 96)
0.0 hour 3200.0 hours or (by each steps)
0 hour 0 minutes 300 hours 59 minutes or (by each steps)
0 minutes 0 second 300 minutes 59 seconds or (by each steps)
0.1 hour or 1 second
±( setting time × 0.02% + 0.1 second)
SV, step time, PID No, Independent EV
At step to next step -1000.0 1000.0s (setting resolution 0.5s)
At pattern end -1000.0 1000.0s (setting resolution 0.5s)
At program end -1000.0 1000.0s (setting resolution 0.5s)
By each 1step (possible to set ON or OFF)
Max 30000 or
ON/OFF
OFF, 19999 units
Possible by front key, DI allotment or communication
Possible by front key, DI allotment or communication
ON/OFF (Step time which is at power failure is not guaranteed)
Communication function (option)
(1) Communication port
(2) Communication method
(3) Synchronization method
(4) Communications distance
(5) Communication speed
(6) Data format
(7) Master mode
(8) Slave address
(9) Parameter preservation mode
(10) Error detection
(11) Flow control
(12) Delay
(13) Communication code
(14) Protocol
(15) Other condition
(16) Number of connection
(17) Termination resistance
1ch
RS-232C : 3 line system half-duplex system
RS-485 : 2 line system half-duplex
multi-drop (bus) system
The start stop synchronization system
RS-232C : Max15m, RS-485 : Max 500m (depend on a condition)
1200, 2400, 4800, 9600, 19200, 38400 bps
Start1 Stop1,2 Data 7.8bit Non parity odd number, even number
Possible to chosen from SVOUT1OUT2(1:n Number of slave max 255)
When MAC6 is a master, slave address range must be continuation.
When MAC6 is a master, bus connection with other host PCs is not allowed.
Input range of master machine and slave machine should be equal, at the time of
cascade control.
1255
Choose from RAM, MIX and EEP mode.
None, Choose from ADD, complement of ADD +2, exclusive OR, CRC-16 and LRC
None
1500ms (resolution1ms)
ASCII code or binary code
SHIMAX Standard or MODBUS ACII, MODBUS RTU protocol
When P10 or JP10 chosen the data width with a parameter beyond 16bit, only to 1
digit of decimal point below.
RS-232C/1set, RS-485/Maximum 256 sets (depends on conditions, host is included)
RS-232C/Non need, RS-485/120Ω (External connection)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Shimax MAC6A and is the answer not in the manual?

Shimax MAC6A Specifications

General IconGeneral
BrandShimax
ModelMAC6A
CategoryController
LanguageEnglish

Related product manuals