EasyManuals Logo

SICK CLV61 Series Technical Information

SICK CLV61 Series
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #47 background imageLoading...
Page #47 background image
Technical Information Chapter 4
CLV61x
Electrical installation
8015592/ZNI9/2017-06-13 © SICK AG · Germany · All rights reserved · Subject to change without notice 47
4.8.9 Wiring the "Result 1" Switching Output in the CDM420-0001 Connection
Module
6
1
10
5
11
15
CLV61x
CDM420-0001
V
S
= DC 10 V to 30 V
Load (e.g. PLC)
D-Sub HD plug,
15-pin
12
5
.
.
.
14
Result 1
13
GND
5
Shield
+24 V* (V
S
)
V
S
GND
Quenching circuit:
Install an anti-surge
diode directly at the
load!
For inductive load:
V
out
Result 1
Result 1
GND
1
Ratings for "Result 1" switching output
PNP switching against the supply voltage V
S
(+24 V*)
(default setting: Device Ready (static),
logic: not inverted [active high])
Short-circuit proof + temperature protected
Galvanically not separated from V
S
(+24 V*)
0 V ≤ V
out
≤ V
S
Guaranteed:
(V
S
− 1.5 V) ≤ V
out
≤ V
S
with I
out
≤ 100 mA
Switching
behavior
Features
Electrical
values

Other manuals for SICK CLV61 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SICK CLV61 Series and is the answer not in the manual?

SICK CLV61 Series Specifications

General IconGeneral
BrandSICK
ModelCLV61 Series
CategoryBarcode Reader
LanguageEnglish

Related product manuals