Table 13: RFU63x/65x: required supply voltage V
S
Supply voltage V
s
for the device
Connection mod‐
ule
Part no. Cable (length) Wire cross-sec‐
tion Supply
voltage V
S
Voltage drop
across the cable
at DC 18 V/I =
max. 1.35 A
Required mini‐
mum supply volt‐
age V
S
to the con‐
nection module
Fuse rating for
supply voltage V
S
DC 18 V ... 30 V
P = max. 26 W
CDB650-204 6052286 (2 m)
6051194 (3 m)
6051195 (5 m)
0.14 mm
2
0.14 mm
2
0.14 mm
2
1.0 V
1.5 V
2.3 V
DC 19.0 V
DC 19.5 V
DC 20.3 V
CDB650-204
(2 A)
CDM420-0006 2056184 (0.35 m)
2049764 (0.9 m)
2055419 (2 m)
2055420 (3 m)
2055859 (5 m)
2061480 (2 m)
2061605 (3 m)
2061481 (5 m)
0.10 mm
2
0.10 mm
2
0.10 mm
2
0.10 mm
2
0.10 mm
2
0.14 mm
2
0.14 mm
2
0.14 mm
2
0.2 V
0.5 V
1.0 V
1.5 V
2.5 V
1.0 V
1.5 V
2.3 V
DC 18.2 V
DC 18.5 V
DC 19.0 V
DC 19.5 V
DC 20.5 V
DC 19.0 V
DC 19.5 V
DC 20.3 V
CDM420-0006
(2 A)
Customer-specific
wiring
6042772 (3 m)
6042773 (5 m)
6048817 (10 m)
2070425 (3 m)
2070426 (5 m)
2070427 (10 m)
6045141 (5 m)
6048319 (10 m)
0.14 mm
2
0.14 mm
2
0.14 mm
2
0.14 mm
2
0.14 mm
2
0.14 mm
2
0.14 mm
2
0.25 mm
2
1.5 V
2.3 V
4.6 V
1.5 V
2.3 V
4.6 V
2.3 V
2.0 V
DC 19.5 V
DC 20.3 V
DC 22.6 V
DC 19.5 V
DC 20.3 V
DC 22.6 V
DC 20.3 V
DC 20.0 V
2 A at the start of
the cable
DC 12 V ... 30 V
P = max. 26 W
6048319 (10 m) 0.25 mm
2
3.0 V at DC 12 V/
1.9 A
DC 15.0 V 2.5 A at the start
of the cable
1
When operating the device via the optional SICK CDB650-204 or CDM420-0006 connection module and using a SICK connecting cable.
When operating the device below 0 °C and using a cold-resistant connecting cable from SICK.
2
When operating the device without a SICK connection module and using a SICK connecting cable. When operating the device below 0 °C
and using the cold-resistant connecting cable from SICK, part no. 6048319 (2 x 2.5 mm
2
, 10 m).
The power source must be able to deliver at least 26 W of power or at least 1.5 A
at 18 V DC.
The voltage supply via a power supply unit must be capable of bridging a brief
power failure of 20 ms.
In the case of connection via the optional connection module CDB/CDM: addition‐
ally required output power 0.5 W when using the optional parameter cloning mod‐
ule CMC600 in the connection module.
Protecting the supply cables
To ensure protection against short-circuits and overload in the customer-supplied
cables, the wire cross-sections used must be selected and protected in accordance
with national regulations.
The following standards must be observed in Germany:
DIN VDE 0100 (part 430)
DIN VDE 0298 (part 4) and/or DIN VDE 0891 (part 1)
Wiring without SICK connection module
For a supply voltage between 18 V and 30 V DC, protect the device with a separate 2 A
slow-blow fuse.
For a supply voltage between 12 V and 30 V DC and when operating the device with the
SICK supply cable part no. 6048319 (2 x 2.5 mm
2
, length 10 m), protect the device
with a separate 2.5 A slow-blow fuse.
b
Install the fuse in the supply circuit at the start of the supply cable.
6 ELECTRICAL INSTALLATION
64
O P E R A T I N G I N S T R U C T I O N S | RFU63x, RFU65x 8014335/ZTL9/2018-10-14 | SICK
Subject to change without notice