Characteristic data of digital switching inputs
Table 47: Characteristic data of the digital switching inputs “External input 1” and “External
input 2”
Switching behavior Power to the input starts the assigned function, e.g. start read cycle.
Default setting in the device: logic not inverted (active high), debounce
time 10 ms
Properties
•
Opto-decoupled, reverse polarity protected
•
Can be wired with PNP output of a trigger sensor
Electrical values Low: V
in
≤ 2 V; I
in
≤ 0.3 mA
High: 6 V ≤ V
in
≤ 30 V; 0.7 mA ≤ I
in
≤ 5 mA
NOTE
Assign the functions for the external digital switching inputs in the device with a config‐
uration tool, e.g. the configuration software SOPAS ET.
14.5.9 Wiring the “Result 1” and “Result 2” digital switching outputs of the device in the CDB650-204
Device = RFU63x-131xx, RFU63x-041xx
Device = RFU65x-101xx
Device 1
CDB650-204
Load (e.g. PLC) 4
Cable 3
B
1
.
.
.
D
22
GND
5Shield
U
IN
*V
S
GND
V
out
Result A
GND
B
1
2 2
For inductive load: 6
3
1
7
2
6
5
4
8
13
14
17
15
9
10
12
16
11
3
1
7
2
6
5
4
8
13
14
17
15
9
10
12
16
11
RES/OUT C
8 7
2
5
Figure 55: Wiring digital switching outputs “Result 1” and “Result 2” of the device in the connection module CDB650-204
1
Device
2
Supply voltage V
S
3
Connection cable 1:1 (female connector, M12, 17-pin, A-coded / male connector, M12, 17-pin, A-coded)
4
Load (e.g. PLC)
5
Output voltage V
out
6
With inductive load: see note
7
Connection module: female connector, M12, 17-pin, A-coded
8
Device: male connector, M12, 17-pin, A-coded
ANNEX 14
8014335/ZTL9/2018-10-14 | SICK O P E R A T I N G I N S T R U C T I O N S | RFU63x, RFU65x
113