Configuration
6 Configuration
PROFINET IO network
An MRP domain and a NameOfStation must be named as per the PNO specification V2.3.
For this reason take into account the following naming convention during the configuration
of your PROFINET IO network:
The identifier comprises one or more words.
These words are separated using a [.].
The total length of the identifier is 1 to 240 characters.
The word length is 1 to 63 characters.
The identifier uses the following syntax:
Words comprise [a-z0-9-].
Words do not start with [-].
Words do not end with [-].
The first word must not have the form port-xyz or port-xyz-abcde
(a, b, c, d, e and x, y, z = 0 … 9).
Identifiers must not have the form n.n.n.n (n = 0 … 999).
Also take into account on naming an MRP domain:
The total length of the identifier must be 3, 7, 11, 15, 19, … characters.
S3000 PROFINET IO/IOOF
The configuration is performed in 3 steps:
1. Configuration PROFINET IO
2. Configuration PROFIsafe
3. Configuration of the S3000 PROFINET IO/IO8OF
Note

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SICK S3000 PROFINET IO Series and is the answer not in the manual?

SICK S3000 PROFINET IO Series Specifications

General IconGeneral
InterfacesPROFINET IO
Protection classIP65
Safety integrity levelSIL2 (IEC 61508)
Operating temperature0 °C ... +50 °C
Supply voltage24 V DC
Performance levelPL d
TypeLaser scanner
Protective field range0.1 m to 3 m