EasyManua.ls Logo

Siemens 7SR11

Siemens 7SR11
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7SR11 & 7SR12 Description Of Operation
©2012 Siemens Protection Devices Limited Chapter 1 Page 68 of 76
Figure 4-8 Logic Diagram: CT Supervision Function (60CTS) – 7SR12
5.4 Broken Conductor (46BC)
The element calculates the ratio of NPS to PPS currents. Where the NPS:PPS current ratio is above 46BC
Setting an output is given after the 46BC Delay.
The Broken Conductor function can be inhibited from
Inhibit 46BC A binary or virtual input.
46BC U/I Guard A minimum load current
c
&
IL1
IL2
IL3
NPS
Filter
I2
IL1
IL2
IL3
PPS
Filter
I1
C
IL1
IL2
IL3
Figure 4-9 Logic Diagram: Broken Conductor Function (46BC)
5.5 Trip/ Close Circuit Supervision (74TCS & 74CCS)
The relay provides three trip and three close circuit supervision elements, all elements are identical in operation
and independent from each other allowing 3 trip and 3 close circuits to be monitored.
One or more binary inputs can be mapped to 74TCS-n. The inputs are connected into the trip circuit such that at
least one input is energised when the trip circuit wiring is intact. If all mapped inputs become de-energised, due to
a break in the trip circuit wiring or loss of supply an output is given.
The 74TCS-n Delay setting prevents failure being incorrectly indicated during circuit breaker operation. This delay
should be greater than the operating time of the circuit breaker.

Table of Contents

Related product manuals