Special settings BACnetobject R/RW Note
ERC heating / cooling selection
Prio 15 : automatic selection
HExgEcmSta
BVAL,304
RW 0: Heating only
1: Cooling only
ERC Kp GainHExgCtr
AVAL,359
RW % / K
ERC Tn TnHExgCtr
PINTVAL,140
RW s
Min.diff.room temp./outs.air temp.f.cool DiffTRTOaMinC
AVAL,358
RW K
Testing and debugging BACnetobject R/RW Note
Heat exchanger device mode
Prio2: Fire / Smoke
Prio5: Protection plant control
HExgDevMod
MVAL,409
RW 1: Off
2: Control mode
3: Maximum
4: Minimum
5: Bypass only
Application functionalities
Energy Recovery
5
100 | 170 A6V10733786_en_c