4.5.1 Input settings
4.5.1.1 Controller board
The following functions can be selected for input signals on the controller board:
Input B1, B2, B3, B4
Parameter BACnet object
Selection for B1 B1Sel,
STR_VIEW,41
Selection for B2 B2Sel,
STR_VIEW,43
Selection for B3 B3Sel,
STR_VIEW,45
Selection for B4 B4Sel,
STR_VIEW,47
Selection BACnet object R/W Signal type Range
None
Supply air temperature TSu R NTC10k -50…80°C
Outside air temperature Toa R NTC10k -50…50°C
Extract air temperature TEx R NTC10k -50…80°C
Exhaust air temperature TEh R NTC10 -50…80 °C
Supply air temperature after heat
exchanger
TSuAfHExg R NTC10k -50…80 °C
Supply air temperature after
preheating coil
TSuAfPreHcl R NTC10k -50…80 °C
Flow temperature preheating coil TFlPreHcl R NTC10k -50…80 °C
Frost protection temperature for
heating coil
TFrPrtHcl R NTC10k -50…80 °C
Input X1
Parameter BACnet object
Selection for X1 X1Sel,
STR_VIEW,53
Selection BACnet object R/W Signal type Range
None - - -
Supply air fan speed feedback
pulse
FanSuSpdFb R 0…300Hz 0…100%
Supply air fan speed feedback
voltage
FanSuSpdFb R 0…10V 0…100%
Extract air quality AQualEx R 0…10V 0…2000ppm
Relative humidity for extract air HuRelEx R 0…10V 0…100%
Particulate matter in room PmR R 0…10V 0…500µg/m3
Configuration
Configuring the hardware