Remark:
Above information is available for all ebm-papst Modbus fans with interface version
>=5.0.
Error and warning codes are shown as decimal value, for example error code ‘17’.
They must be converted into a bit string, for example ‘0000000000010001’.
According to EBM Papst documentation, this means FB (General fan fault) and
PHA (Phase error).
When using a Modbus fan, both fans must be Modbus fans.
6.2.6 Zero pressure calibration
Both devices (POS9.., QBM97..) have integrated pressure sensors and
therefore also inbuilt zero-pressure-calibration mechanisms.
To perform calibration, all pressure hoses must be disconnected and exposed
to the same ambient pressure.
The calibration process can be manually initiated by activating the calibration
parameter.
Available parameters
Parameter BACnetobject R/RW Note
Zero pressure calibration trigger POS9 ZePClbTrgPos9
MVAL, 628
RW 1: Ready
2: Trigger (initiates calibration)
Zero pressure calibration trigger QBM #1 ZePClbTrgQbm
MVAL, 638
RW 1: Ready
2: Trigger (initiates calibration)
Zero pressure calibration trigger QBM #2 ZePClbTrgQbm(2)
MVAL, 790
RW 1: Ready
2: Trigger (initiates calibration)
Engineering of communicative devices
Modbus components
6
A6V10733786_en_c 153 | 170