5.4 Operating mode settings
The settings for the operating modes define the specific settings for the
supply and
exhaust fans
for all operating modes and for the speed, flow and pressure control
strategies. These settings are configured by the installer. The end user has no
option to change the values for the operating modes.
For Comfort, Economy and Unoccupied modes, dedicated settings for
relative
humidity (r.H.), air quality (AQ) and temperature
can be defined.
The temporaty operating modes Fan boost, Fire place and Kitchen hood have no
dedicated r.H., AQ and temperature settings. For these modes, the settings for
Economy mode apply.
Available parameters
Parameter Detail information BACnet object R/RW State
Current operating
mode
(constant, for end-
user)
Prio 7
: Request from digital inputs:
Comfort, Economy, Unoccupied, Protection
Prio 10
: Periodic maintenance or maintenance shutdown
Prio 12
: Away:
Unoccupied
Prio 13
: Manual:
Comfort, Economy, Unoccupied, Protection
Prio 15
: TSP:
Comfort, Economy, Unoccupied
ROpMod
MVAL,168
RW 1: Protection
2: Unoccupied
3: Economy
4: Comfort
Current ventilation
operating mode
HrvSta
MVAL,166
R 1: Protection
2: Unoccupied
3: Economy
4: Comfort
5: Kitchen hood
6: Fire place
7: Fan boost
Configuration parameter
Description BACnet object R/RW State
TSP overrides manual operation upon a change SchedRstManCnf
BVAL,218
RW 0: manual operation is permanent
1: manual operation is overridden with the next
change
Analysis
Parameter Detail information R/RW State
Present plant
operating mode
Plant operating mode including protection functions
Prio 3
: Emergency
Prio 4:
A-Alarm or power-up
Prio 9
: De-icing
Prio 12
: Request from digital inputs, also temporary boost
Prio 13
: If in temporary mode
RW 1: Off by A-Alarm
2: Protection
3: Economy
4: Pre-Comfort
5: Comfort
6…9: Not used
10: Free Cooling
11: Not used
12: Boost, fireplace or kitchen
13: Not used
14: Off by emergency
15: Smk positive press
16: Smk negative press
17: Smk Purge
18: Frost water
19: Startup/Shup down
20: De-icing with fans
Application functionalities
Operating mode settings
5
A6V10733786_en_c 59 | 170