5.20 Time counters
Various time counters are running automatically on the background depending on
which operating mode is active. Counters can be reset by manually setting the
value to zero.
Available parameters
Operation time BACnetobject R/RW Note
Power-up time of controller OphDev
AVAL,156
RW hrs
Operation time in protection mode OphPrt
AVAL,256
RW hrs
Operation time in unoccupied mode OphUcd
AVAL,266
RW hrs
Operation time in economy mode OphEco
AVAL,267
RW hrs
Operation time in comfort mode OphCmf
AVAL,268
RW hrs
Operating time fireplace ventilation OphFplcVnt
ACAL,146
RW hrs
Operating time kitchen ventilation OphKtchVnt
AVAL,310
RW hrs
Operating time ERC heating OphErcH
AVAL,398
AVAL,402
RW hrs
Operating time ERC cooling OphErcC
AVAL,399
AVAL,401
RW hrs
Operating time electric heating coil OphHcl
AVAL,212
RW hrs
Operating time water heating coil OphHcl
AVAL,220
RW hrs
Operating time preheating brine OphPreHcl
AVAL,396
RW hrs
Operating time preheating earth OphPreHcl
AVAL,397
RW hrs
Operating time electric preheater OphPreHcl
AVAL,348
RW hrs
Operating time DX cooling OphCcl
AVAL,404
RW hrs
Operating time water cooling coil OphCcl AVAL,403 RW hrs
Application functionalities
Time counters
5
134 | 170 A6V10733786_en_c

Table of Contents