5.17 Priority list
Different functions require priorities over other functions so that logical/critical
operation can be guaranteed.
Example
Safety functions
1 Off by smoke detector, emergency, supply air temperature or extract air
temperature
2 Off by fire damper closed
3 Purge or smoke extract by smoke detector
Protection functions
4 Off by water heating coil frost
5 A-Alarms for plant protection
6 ERC deicing function
Switch or push button operations
7 Rapid ventilation mode (Configured BI, POS8)
8 Comfort mode (Conf. BI), Fireplace (Conf. BI), Off mode (Conf. BI), Eco
mode (Conf. BI)
9 Kitchen ventilator (Conf. BI)
10 Maintenance function
User operation
11 Temporary fireplace (POS8)
12 Present / Away button
13 Manual operation
Automatic function
14 Scheduler operation mode
Application functionalities
Priority list