FireDmp1
FireDmp2
Available parameters
Current values BACnetobject R/RW Note
Fire damper status FdpSta
MVAL,160
R 1 = moving
2 = closed
3 = open
4 = no move
5 = no close
6 = no open
Fire damper feedback FdpFb
DI,73 (D1)
BI,90 (D2)
BI,107 (X3)
BI,124 (X8)
R 0 : one or more dampers not
opened or closed
1: all fire dampers in open or
closed end position
Fire damper open
Prio2: Fire / Smoke
Prio5: Protection from plant control
FdpCmd
BO,51 (Q1)
BO,66 (Q2)
BO,81 (Q3)
BVAL,242 (POS9)
RW
Fire damper alarm FdpAlm
BVAL,165
R Fire damper closes
unexpectedly or test failed
Fire damper test active FdpTst
BVAL,212
R Fire damper test actually
running
Basic settings BACnetobject R/RW Note
Activate fire damper test MntnSched
SCHED,3
Activation via weekly
maintenance with BACnet
scheduler
Damper opening time TiOpnFdp
PINTVAL,117
RW sec.
Damper closing time TiClsFdp
PINTVAL,118
RW sec.
Testing and debugging BACnetobject R/RW Note
Fire damper closed by control
program
FireAlm
BVAL,163
R
Application functionalities
Fire damper (Fdp11y)
5
128 | 170 A6V10733786_en_c