6.3.8 Device information
The device information occupies a total 1024 registers, starting with holding
registers 4x9000.
4x9000~4x9767: Are reserved for basic device information such as LocalDate,
LocalTime, DeviceID, Language selection, etc.
Register
Address
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 Read/
Write
9001 System-Status
Local-Date Write
access
9002 Year (100…199, 0xFF) Month (1…12, 0xFF)
9003 DayOfMonth (1…31, 0xFF) DayOfWeek (1…7, 0xFF)
Local-Time
9004 Hours (00…23; 0xFF) Minutes (00…59; 0xFF)
9005 Seconds (00…59; 0xFF) HundrethsOfASecond (00…99; 0xFF)
9006
9037
Equipment-ID (string -> 32 Registers)(Property:4895) Read only
9038
9069
Serial-Number (string -> 32 Registers) (Property:5100)
9070
9101
Model-Information (string -> 32 Registers) (Property:4827)
9102
9165
Firmware-Revision (string -> 64 Registers) (Property:44)
9166
9229
Application-Software-Version (string -> 64 Registers) (Property:12)
9230
9233
Supported-Languages (bitset, 64 bits) (Property:4948)
9234 Active-Language (enum) (Property:4949)
9235
9767
Reserved registers (532) for future extensions
(additional data items for the Device-Object or other infrastructure related objects)