Input X2
Parameter BACnet object
Selection for X2 X2Sel,
STR_VIEW,55
Selection BACnet object R/W Signal type Range
None - - -
Exhaust air fan speed feedback
pulse
FanEhSpdFb R 0…300Hz 0…100%
Exhaust air fan speed feedback
voltage
FanEhSpdFb R 0…10V 0…100%
Extract air quality AQualEx R 0…10V 0…2000ppm
Relative humidity for extract air HuRelEx R 0…10V 0…100%
Particulate matter in room PmR R 0…10V 0…500µg/m3
Input X3
Parameter BACnet object
Selection for X3 X3Sel,
STR_VIEW,57
Selection BACnet object R/W Signal type Note
None - - -
Extract air quality AQualEx R 0…10V 0…2000ppm
Relative humidity for extract air HuRelEx R 0…10V 0…100%
Particulate matter in room PmR R 0…10V 0…500µg/m3
Rapid ventilation input RpdVntIn R Contact NO
Kitchen hood ventilation input KtchVntIn R Contact NO
Fireplace ventilation input FplcVntIn R Contact NO
Air filter differential pressure
monitor
FilAirDiffPMon R Contact NO
Fire damper feedback FdpFb R Contact NO
Preheating coil overtemperature
detector
PreHclOvrTDet R Contact NC
Heat exchanger condensation
monitor
HExgCdnMon R Contact NO
Rotary heat exchanger fault RotHExgFlt R Contact NO
Heat exchanger differential
pressure monitor
HExgDiffPMon R Contact NO
Heating coil overtemperature
detector
HclOvrTDet R Contact NC
Cooling coil DX evaporator fault CclDxFlt R Contact NO
Emergency off EmgOff R Contact NC
Smoke extraction Smext R Contact NO
Input room operating mode comfort CmfOpModRIn R Contact NO
Input room operating mode
economy
EcoOpModRIn R Contact NO
Input room operating mode
unoccupied
UcdOpModRin R Contact NO
Input room operating mode
protection
PrtOpModRIn R Contact NO
Configuration
Configuring the hardware
4
38 | 170 A6V10733786_en_c