Input X8
Parameter BACnet object
Selection for X8 X8Sel,
STR_VIEW,59
Selection BACnet object R/W Signal type Range
None - - -
Extract air temperature TEx R NTC10k -50…80°C
Exhaust air temperature TEh R NTC10k -50…80°C
Supply air temperature after heat
exchanger
TSuAfHExg R NTC10k -50…80°C
Supply air temperature after
preheating coil
TSuAfPreHcl R NTC10k -50…80°C
Flow temperature preheating coil TFlPreHcl R NTC10k -50…80°C
Frost protection temperature for
heating coil
TFrPrtHcl R NTC10k -50…80°C
Rapid ventilation input RpdVntIn R Contact NO
Kitchen hood ventilation input KtchVntIn R Contact NO
Fireplace ventilation input FplcVntIn R Contact NO
Air filter differential pressure
monitor
FilAirDiffPMon R Contact NO
Fire damper feedback FdpFb R Contact NO
Preheating coil overtemperature
detector
PreHclOvrTDet R Contact NC
Heat exchanger condensation
monitor
HExgCdnMon R Contact NO
Rotary heat exchanger fault RotHExgFlt R Contact NO
Heat exchanger differential
pressure monitor
HExgDiffPMon R Contact NO
Heating coil overtemperature
detector
HclOvrTDet R Contact NC
Cooling coil DX evaporator fault CclDxFlt R Contact NO
Emergency off EmgOff R Contact NC
Smoke extraction Smext R Contact NO
Input room operating mode comfort CmfOpModRIn R Contact NO
Input room operating mode
economy
EcoOpModRIn R Contact NO
Input room operating mode
unoccupied
UcdOpModRin R Contact NO
Input room operating mode
protection
PrtOpModRIn R Contact NO
Configuration
Configuring the hardware
4
A6V10733786_en_c 39 | 170