Input D1, D2
Parameter BACnet object
Selection for D1 D1Sel,
STR_VIEW,49
Selection for D2 D2Sel,
STR_VIEW,51
Selection BACnet object R/W Signal type Range
None - - -
Rapid ventilation input RpdVntIn R Contact NO
Kitchen hood ventilation input KtchVntIn R Contact NO
Fireplace ventilation input FplcVntIn R Contact NO
Air filter differential pressure
monitor
FilAirDiffPMon R Contact NC / NO
Fire damper feedback FdpFb R Contact NC / NO
Preheating coil overtemperature
detector
PreHclOvrTDet R Contact NC / NO
Heat exchanger condensation
monitor
HExgCdnMon R Contact NC / NO
Rotary heat exchanger fault RotHExgFlt R Contact NC / NO
Heat exchanger differential
pressure monitor
HExgDiffPMon R Contact NC / NO
Heating coil overtemperature
detector
HclOvrTDet R Contact NC / NO
Cooling coil DX evaporator fault CclDxFlt R Contact NC / NO
Emergency off EmgOff R Contact NC / NO
Smoke extraction Smext R Contact NC / NO
Input room operating mode comfort CmfOpModRIn R Contact NO
Input room operating mode
economy
EcoOpModRIn R Contact NO
Input room operating mode
unoccupied
UcdOpModRin R Contact NO
Input room operating mode
protection
PrtOpModRIn R Contact NO
Configuration
Configuring the hardware
4