Basic settings BACnetobject R/RW Note
De-icing mode configuration (for
differential pressure indication only)
DeicModCnf
MVAL,410
RW 1: None
2: Erc fix
3: Erc fix + Fans
4: Erc fix + Preh
5: Erc fix + Fans + Preh
6: Erc TEh
7: Erc TEh + Fans
8: Erc TEh + Preh
9: Erc TEh + Fans + Preh
De-icing, stage1 limit, heat exchanger
only
SpTDeicHExg
AVAL,367
RW °C
De-icing, stage2 limit, fan SpTDeicFan
AVAL,363
RW °C
Activation time deicing TiDeic
PINTVAL,142
RW sec.
De-icing bypass damper position HxDmpbPosDeic
AVAL,368
RW % , for open damper
configure 100%
De-icing supply fan flow SpAirFlSuDeic
AVAL,181
RW m3/h
De-icing exhaust fan flow SpAirFlEhDeic
AVAL,226
RW m3/h
De-icing supply fan pressure SpPSuDeic
AVAL,196
RW Pa
De-icing exhaust fan pressure SpPExDeic
AVAL,232
RW Pa
De-icing supply fan speed SpFanSuSpdDeic
AVAL,208
RW %
De-icing exhaust fan speed SpFanEhSpdDeic
AVAL,295
RW %
Special settings BACnetobject R/RW Note
Temperature drop for room / extract
humidity <= 20%
DiffTHuCmpDeic
AVAL,366
RW K
Temperature for maximum off time TDeicTiOffStt
AVAL,369
RW °C
Maximum off time TiOffDeicMax
PINTVAL,143
RW sec.
Temperature for minimum off time TDeicTiOffEnd
AVAL,370
RW °C
Minimum off time TiOffDeicMin
PINTVAL,144
RW sec.
Application functionalities
Energy Recovery
5
104 | 170 A6V10733786_en_c