Available parameters
Actual values BACnetobject R/RW Note
Outside air damper position
Prio 2: Fire / Smoke
Prio 5: Protection from plant control
DmpOaPos
AO,163 (A1)
AO,166 (A2)
AO,168 (A3)
AO,169 (A4)
AVAL,741 (AO1)
AVAL,745 (AO2)
RW Outside air
damper
Mixing air damper position
Prio 2: Fire / Smoke
Prio 5: Protection from plant control
DmpMixPos
AO,162 (A1)
AO,165 (A2)
AO,167 (A3)
AO,170 (A4)
AVAL,740 (AO1)
AVAL,744 (AO2)
RW Recirculating air
damper
Recirculating damper heating/
cooling state
MixDmpHCSta
MVAL,943
R 1: Neither
2: Heating
3: Cooling
Basic settings BACnetobject R/RW Note
Outside damper delay time DlyOnAflVntReq
PINTVAL,667
RW S
Outside damper minimum position OADmpMin
PINTVAL,729
RW Default 30%
Special settings BACnetobject R/RW Note
Damper TSu Kp GainDmpCtr
AVAL,735
RW %/K
Damper TSu Tn TnDmpCtr
PINTVAL,668
RW S
Application functionalities
Outside air dampers (DmpShoffOa11y)
5
120 | 170 A6V10733786_en_c