Available parameters
Acknowledge and Reset BACnetobject R/RW Note
A-Alarm acknowledgement and reset AalmAck
MVAL,137
RW 1: Ready
2: Acknowledge
3: Reset
Automatic return to 1
B-Alarm acknowledgement BalmAck
MVAL,133
RW 1: Ready
2: Acknowledge
Automatic return to 1
A-Alarms BACnetobject R/RW Note
A-Alarm state AalmSta
MVAL,135
R 1: Acknowledged, unlocked
2: Unacknowledged
3: Locked
A-Alarm indication AalmInd
MVAL,136
R 1: Normal
2: Alarm
A-Alarm code AalmCode
AVAL,49
R 0...9999
B-Alarms BACnetobject R/RW Note
B-Alarm state BalmSta
MVAL,132
R 1: Acknowledged, unlocked
2: Unacknowledged
3: Locked
B-Alarm indication BalmInd
MVAL,131
R 1: Normal
2: Alarm
B-Alarm code BalmCode
AVAL,43
R 0...9999
Alarm class settings BACnetobject R/RW Note
Alarm configuration for outside air
temperature
AlmCnfTOa
MVAL,141
RW 1: A-Alarm
2: B-Alarm
Alarm configuration for heat exchanger AlmCnfHExg
MVAL,348
RW 1: A-Alarm
2: B-Alarm
3: None
Alarm configuration for all fan errors
(feedback fault, error signal or Modbus
interrupted)
AlmCnfFanFb
MVAl,349
RW 1: A-Alarm
2: B-Alarm
3: None (No fan error
supervision. – Do not use
‘None’ for Modbus fans)
Application functionalities
Alarm functions
5
A6V10733786_en_c 137 | 170