EasyManua.ls Logo

Siemens Climatix S300 HRV - Page 157

Siemens Climatix S300 HRV
170 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Write Single Register, FC=06
Request
Function code 1 Byte
0x06
Register Address 2 Bytes 0x0000 to 0xFFFF
Register Value 2 Bytes 0x0000 to 0xFFFF
Response
Function code 1 Byte
0x06
Register Address 2 Bytes 0x0000 to 0xFFFF
Register value 2 Bytes 0x0000 to 0xFFFF
Error
Error code 1 Byte
0x86
Exception code 1 Byte 01 or 02 or 03 or 04
Write Multiple Register, FC=16
Request
Function code 1 Byte
0x10
Starting Address 2 Bytes 0x0000 to 0xFFFF
Quantity of Registers 2 Bytes 0x0001 to 0x007B
Byte Count 1 Byte 2 x
N*
Registers Value
N
* x 2 Bytes value
*N=Quantity of Registers
Response
Function code 1 Byte
0x10
Starting Address 2 Bytes 0x0000 to 0xFFFF
Quantity of Registers 2 Bytes 1 to 123 (0x7B)
Error
Error code 1 Byte
0x90
Exception code 1 Byte 01 or 02 or 03 or 04
A block of contiguous registers is written in one step.
Quantity of registers n = 1...123.
The requested written values are specified in the request data field.
Data is packed as 2 bytes per register, i.e. byte count = 2 x n.
In the request message the 2 bytes of the first register (Starting Address) are
sent first.
Engineering of communicative devices
Modbus slave
6
A6V10733786_en_c 157 | 170

Table of Contents

Related product manuals