Input AI1
Parameter BACnet object
Selection for AI1 AI1Sel,
QBM97#1: STR_VIEW,333
QBM97#1: STR_VIEW,429
Selection BACnet object R/W Signal type Range
None - - -
Outside air temperature TOa R NTC10k -50…50 °C
Extract air temperature TEx R NTC10k -50…80 °C
Exhaust air temperature TEh R NTC10k -50…80 °C
Supply air temperature after heat
exchanger
TSuAfHExg R NTC10k -50…80 °C
Supply air temperature after
preheating coil
TSuAfPreHcl R NTC10k -50…80 °C
Flow temperature preheating coil TFlPreHcl R NTC10k -50…80 °C
Frost protection temperature for
heating coil
TFrPrtHcl R NTC10k -50…80 °C
Input AI2
Parameter BACnet object
Selection for AI2 AI2Sel,
QBM97#1: STR_VIEW,335
QBM97#1: STR_VIEW,460
Selection BACnet object R/W Signal type Range
None - - -
Extract air quality AQualEx R 0…10V 0…2000 ppm
Relative humidity for extract air HuRelEx R 0…10V 0…100 %
Particulate matter in room PmR R 0…10V 0…500 µg/m3
Configuration
Configuring the hardware
4
A6V10733786_en_c 43 | 170