Oper. mode settings BACnet object R/RW Note
Unoccupied: supply SpPSuUcd
AVAL,281
RW Pa
Economy: supply SpPSuEco
AVAL,280
RW Pa
Comfort: supply SpPSuCmf
AVAL,279
RW Pa
Fire: supply SpPSuFplc
AVAL,71
RW Pa
Kitchen hood: supply SpPSuKtch
AVAL,282
RW Pa
Special settings BACnet object R/RW Unit
Supply fan Kp GainPSuCtr
AVAL,200
RW %/Pa
Supply fan Tn TnPSuCtr
PINTVAL,102
RW s
K-factor, supply fan AirFlSuCoef
AVAL,203
RW m3/h per Pa
Tacho signal mapping
Pulses/sec for 100% fan
speed
FanSuSpdFb
AI,65
RW Property 4965
Range 0…300 pulse/s
Testing / debugging BACnet object R/RW State
Fan device mode
Prio 2: Fire / Smoke
Prio 5: Protection
FanSuDevMod
MVAL,148
RW 1: Off
2: Control mode
3: Max.air vol.flow
4: Min.air vol.flow
5: Manual speed
6: Smoke ctrl. duct pressure
De‑icing air
7: Vol.flow
8: Startup
Application functionalities
Fan speed control
5