Available parameters
Current value BACnet object R/RW Unit
Air quality value Extract AQualEx
AI,67 (X1)
AI,71 (X2)
AI,73 (X3)
AVAL,318 (POS9, X22)
AVAL,469 (QBM, AI2)
R ppm
Air quality value Room AQualR
AI,105 (QMX.P70)
R ppm
Present ventilation setpoint for air
quality control (flow)
PrSpAQual
AVAL,50
RW Ppm
Actual setpoint given by
operating mode
Parameters for VntCtl11y BACnet object R/RW Unit
Unoccupied: AQ setpoint SpAQualRUcd
AVAL,269
RW ppm
Economy: AQ setpoint SpAQualREco
AVAL,53
RW ppm
Comfort: AQ setpoint SpAQualRCmf
AVAL,51
RW ppm
Ventilation Kp GainVntCtr
AVAL,64
RW %/ppm
Ventilation Tn TnVntCtr
PINTVAL,71
RW s
Special settings BACnet object R/RW Note
Sensor ppm for 0V signal AQualExPrcv1
AVAL,533 (X1)
AVAL,534 (X2)
AVAL,535 (X3)
PINTVAL,609 (POS9)
PINTVAL,610 (QBM)
R
Sensor ppm for 10V signal AQualExPrcv2
AVAL,536(X1)
AVAL,537 (X2)
AVAL,538 (X3)
PINTVAL,611 (POS9)
PINTVAL,612 (QBM)
R
Testing and debugging BACnet object R/RW Unit
Air quality controller output FanVntReq
AVAL,184 (Air flow)
AVAL,194 (Duct press)
AVAL,205 (Lin. Fan spd)
R %
Application functionalities
Air quality control (VntCtl11y, 12y, 13y)