Siemens Climatix S300 HRV - Page 79

Siemens Climatix S300 HRV
170 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Special settings BACnet object R/RW Note
Run time Pm controller TiRnPmCtl
PINTVAL,562
RW s
Interruption time Pm controller TiIrptPmCtl
PINTVAL,563
RW s
Sensor µg/m3 for 0V signal PmRPrcv1
AVAL,539 (X1)
AVAL,540 (X2)
AVAL,541 (X3)
PINTVAL,613 (POS9)
PINTVAL,614 (QBM)
RW BACnet property 4999
Sensor µg/m3 for 10V signal PmRPrcv2
AVAL,542 (X1)
AVAL,543 (X2)
AVAL,544 (X3)
PINTVAL,615 (POS9)
PINTVAL,616 (QBM)
RW BACnet property 4998
Testing and debugging BACnet object R/RW Note
PM controller output PrSpPmR
AVAL,449
R %
Application functionalities
Air quality control (VntCtl11y, 12y, 13y)
5
A6V10733786_en_c 79 | 170