Available parameters
Current values BACnet object R/RW Unit / Note
Supply air temperature TSu
AI,52
R °C
Outside air temperature TOa
AI,51
R °C
Present temperature setpoint SpT
AVAL,598
RW °C
includes weather
compensation
Present setpoint shift heating PrSpShftH
AVAL,96
R K
shows winter
compensation
Present setpoint shift cooling PrSpShftC
AVAL,128
R K
shows summer
compensation
Standard parameters BACnet object R/RW Unit
Setpoint supply air temperature comfort SpTCmf
AVAL,97
RW °C
Setpoint difference cooling for comfort DSpCCmf
AVAL,392
RW K
Setpoint difference heating comfort DSpHCmf
AVAL,390
RW K
Setpoint supply air temperature economy SpTEco
AVAL,296
RW °C
Setpoint difference cooling economy DSpCEco
AVAL,306
RW K
Setpoint difference heating economy DSpHEco
AVAL,299
RW K
Setpoint supply air temperature unoccupied SpTUcd
AVAL,297
RW °C
Setpoint difference cooling for unoccupied DSpCUcd
AVAL,307
RW K
Setpoint difference for heating unoccupied DSpHUcd
AVAL,300
RW K
Special settings BACnet object R/RW Unit
TOa limitation for heating release HLmCmf
AVAL,105
RW °C
TOa limitation for cooling release CLmCmf
AVAL,132
RW °C
Setpoint heating protection SpHPrt
AVAL,100
RW °C
Setpoint cooling protection SpCPrt
AVAL,129
RW °C
Testing and debugging BACnet object R/RW State
Heating / cooling state HCSta
MVAL,128
R 1: Neither
2: Heating
3: Cooling
Delay heating cooling changeover DlyOnHCChovr
PINTVAL, 68
RW
Application functionalities
Air temperature control
5
A6V10733786_en_c 85 | 170