Available parameters
Winter compensation BACnetobject R/RW Note
Starting point SttSpShftH
AVAL,106 (Supply)
AVAL,121 (Cascade)
RW Compensation point 1
Ending point EndSpShftH
AVAL,107 (Supply)
AVAL,122 (Cascade)
RW Compensation point 2
Setpoint shift SpShftH
AVAL,108 (Supply)
AVAL,123 (Cascade)
RW Compensation point 3
Summer compensation BACnetobject R/RW Note
Starting point SttSpShftC
AVAL,133 (Supply)
AVAL,142 (Cascade)
RW Compensation point 4
Ending point EndSpShftC
AVAL,134 (Supply)
AVAL,143 (Cascade)
RW Compensation point 5
Setpoint shift SpShftC
AVAL,135 (Supply)
AVAL,144 (Cascade)
RW Compensation point 6
Application functionalities
Air temperature control
5
A6V10733786_en_c 87 | 170