Available parameters
Current values BACnet object R/RW Unit
Extract air temperature TEx
B3:AI,53
B4:AI,59
X8:AI,75
X21:AVAL,312
AI1:AVAL,463
R °C
Room temperature TR
AI,99 (POS4420)
AI,120 (POS4440)
AI,103 (QMX.P70)
AI,101 (QMX.P40)
AI,100 (QMX.P30)
R °C
Supply air temperature TSu
AI,52
R °C
Outside air temperature TOa
AI,51
R °C
Present temperature setpoint SpT
AVAL,598
RW °C
includes
weather
compensation
Present setpoint shift heating PrSpShftH
AVAL,111
R K
shows winter
compensation
Present setpoint shift cooling PrSpShftC
AVAL,137
R K
shows summer
compensation
Standard parameters BACnet object R/RW Unit
Setpoint room / extract temperature comfort SpTCmf
AVAL,112
RW °C
Setpoint difference cooling for comfort DSpCCmf
AVAL,393
RW K
Setpoint difference heating for comfort DSpHCmf
AVAL,391
RW K
Setpoint room / extract temperature economy SpTEco
AVAL,301
RW °C
Setpoint difference cooling for economy DSpCEco
AVAL,308
RW K
Setpoint difference for heating economy DSpHEco
AVAL,304
RW K
Setpoint room / extract temperature unoccupied SpTUcd
AVAL,302
RW °C
Setpoint difference cooling for unoccupied DSpCUcd
AVAL,309
RW K
Setpoint difference for heating unoccupied DSpHUcd
AVAL,305
RW K
Max setpoint for supply air temperature SpTSuMax
AVAL,126
RW °C
Min. setpoint for supply air temperature SpTsuMin
AVAL,125
RW °C
Application functionalities
Air temperature control
5
A6V10733786_en_c 89 | 170