Basic settings BACnetobject R/RW Note
De-icing mode configuration DeicModCnf
MVAL,408
RW 1: None
2: Erc fix
3: Erc fix + Fans
4: Erc fix + Preh
5: Erc fix + Fans + Preh
6: Erc TEh
7: Erc TEh + Fans
8: Erc TEh + Preh
9: Erc TEh + Fans + Preh
De-icing, stage1 limit, heat exchanger SpTDeicHExg
AVAL,177
RW °C
De-icing, stage2 limit, fan SpTDeicFan
AVAL,173
RW °C
Activation time de-icing TiDeic
PINTVAL,90
RW sec.
De-icing rotor speed HExgSpdDeic
AVAL,178
RW %
De-icing supply fan flow SpAirFlSuDeic
AVAL,181
RW m3/h
De-icing exhaust fan flow SpAirFlEhDeic
AVAL,226
RW m3/h
De-icing supply fan pressure SpPSuDeic
AVAL,196
RW Pa
De-icing exhaust fan pressure SpPExDeic
AVAL,232
RW Pa
De-icing supply fan speed SpFanSuSpdDeic
AVAL,208
RW %
De-icing exhaust fan speed SpFanEhSpdDeic
AVAL,238
RW %
Special settings BACnetobject R/RW Note
Temperature drop for room extract
humidity of 20% r.h.
DiffTHuCmpDeic
AVAL,176
RW K
Temperature for maximum off time TDeicTiOffStt
AVAL,179
RW °C
Maximum off time TiOffDeicMax
PINTVAL,91
RW sec.
Temperature for minimum off time TDeicTiOffEnd
AVAL,180
RW °C
Minimum off time TiOffDeicMin
PINTVAL,92
RW sec.