Performance data   
2.5 PROFINET IO characteristic data 
  CP 343-1 
22  Manual, 12/2018, C79000−G8976−C201-08 
Configuration limits of the CP as a PROFINET IO device and I-device 
The CP supports the following configuration if it is configured as a PROFINET IO device and 
as an I-device: 
Table 2- 7  Configuration limits of the CP as a PROFINET IO device 
Size of the transfer area 
Number of transfer areas  32 
The size of the user data is calculated from the maximum frame size (gross 548 bytes) 
minus the following values: 1 for the CP itself, 1 per Interface, 1 per port, 1 for each plugged-
in module in HW Config or per slot used. 
Table 2- 8  Example of calculating the user data of the CP 343-1 as an IO device 
-1
for the CP itself 
for the maximum number of pluggable modules 
Net size of the user data * 
* By using fewer but larger modules, the amount of user data can be increased. 
Execution times of the FC blocks PNIO_SEND / PNIO_RECV 
The execution time required to process the function blocks (PNIO_SEND, PNIO_RECV) 
required on the S7-300 CPU is decisive for the calculation of the reaction times in 
PROFINET IO. 
 