Installation, connecting up and commissioning 
  5.2 Installing the CP, connecting power and ground 
CP 343-1 
Manual, 12/2018, C79000−G8976−C201-08 
37 
 
Suitable cables for temperatures in excess of 70 °C  
If the cable or conduit entry point exceeds 70°C or the branching point of conductors 
exceeds 80°C, special precautions must be taken. If the device is operated at ambient 
temperatures above 50°C, the permitted temperature range of the selected cable must be 
suitable for the temperatures actually measured. 
 
Protection against transient voltage surges  
Provisions shall be made to prevent the rated voltage from being exceeded by transient 
voltage surges of more than 40%. This criterion is fulfilled, if supplies are derived from 
SELV (Safety Extra-Low Voltage) only.  
 
Installing the CP, connecting power and ground 
 
Note 
Pulling/plugging 
Pulling/plugging the CP when the power is on is not permitted.
 
You should also remember that by removing a module from the rack, all modules on the 
other side of it will be disconnected from the CPU.