Configuration and operation
6.10 SNMP agent
CP 343-1
Manual, 12/2018, C79000−G8976−C201-08
53
Supported MIBs
The CP supports the following groups of MIB objects of the standard MIB II according to
RFC1213:
System
Interfaces
Address Translation (AT)
IP
ICMP
TCP
UDP
SNMP
The other groups of the MIB II standard are not supported:
EGP
Transmission
The CP also supports the LLDPMIB according to IEEE 802.1AB, the PROFINET expansions
of the LLDPMIB (see also IEC 61158106), the Automation System MIB and the
MRP Monitoring MIB.
Exceptions / restrictions:
Write access is permitted only for the following MIB objects of the system group:
sysContact
sysLocation
sysName
A set sysName is sent as the host name using DHCP option 12 to the DHCP server to
register with a DNS server.
For all other MIB objects / MIB object groups, only read access is possible for security
reasons.
Traps are not supported by the CP.
"Interfaces" MIB group
This group returns status information about the CP interfaces. The MIB objects of the ifTable
provide the status information of the interfaces. The "ifIndex" object identifier is assigned to
the CP interfaces as follows:
Table 6- 1 Assignment of ifIndex
ifIndex
Type of interface
1-2
Port 1-2
3 Internal CP interface

Table of Contents

Other manuals for Siemens CP 343-1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CP 343-1 and is the answer not in the manual?

Siemens CP 343-1 Specifications

General IconGeneral
Product Type DesignationCP 343-1
Power Supply24 V DC
Protection ClassIP20
Product TypeCommunications processor
InterfaceEthernet
Data Transmission Rate10/100 Mbit/s
Protocols SupportedTCP/IP, UDP
Number of Ports1
Operating Temperature0 to 60 °C