14
GENERAL SPECIFICATIONS
Operating specifications for the FC2005 are as follows:
Environmental
Operating temperature - 32 – 120 F (0 – 49 C)
Relative humidity - Up to 93% @ 90 F (32 C)
To be installed in an indoor dry protected environment only
Primary Power Supply (FP2011-U1)
Input: 120 VAC, 60 Hz or 240 VAC, 50 Hz
@ 2.0 A max.
Supervised
Output: 26 VDC @ 6.5 A max.
Max current: 6.5 A (2 hours max.)
Filtered and Regulated
Secondary Power Supply
24 V lead-acid battery set
Max. charged voltage: 27.8 VDC
Automatic low battery disconnect voltage: 19.20.1 VDC
Max. charge current: 0.45 A
Battery capacity:12 Ah (for US and Canada) internally to 18 Ah (for US only) with separate
enclosure FH2072-UA
Supervised
Auxiliary Power Outputs
Non-resettable power output
Power limited
Current: 0.75 A
Voltage: 19 to 28 VDC
Ripple: 0.1 VAC
Special Application
Resettable power output
Power limited
Current: 0.75 A
Voltage: 19 to 28 VDC
Ripple: 0.1 VAC
Special Application