37
Wiring Separation
All high voltage and non-power limited wiring must be kept separate from power limited wiring.
A separation of at least 1/4 inch must be maintained with high voltage and non-power limited
wiring running in separate conduit openings from power limited wiring.
Internal Structure
AC input
NAC-2
NAC-1
P2
Dialer
Relay-1
Relay-2
7 Optional field wire knock-outs
Power limited
Non power limited
Relay-3
Relay-4
Enclosure
Power supply
Batteries
Battery bracket
left
Battery bracket
right
Main board assembly