16
Max. 50 addressable devices
City Tie Circuits
Supply Input:
Voltage: 26 VDC
18 28 VDC for battery
Current: Max. 0.4 A
Supervised
Output:
City Tie-Output 1
Normal output voltage: 19-28 VDC (open circuit condition)
Supervisory current: 1 mA
Maximum trip current: 400 mA
Maximum coil plus wire resistance: 22.5
Leased line-Output 1
Normal output voltage: 19-28 VDC (open circuit condition)
Trouble output voltage: 0 V
Alarm output voltage: -(19-28) VDC (open circuit condition)
Maximum wire resistance: 2-5 k
Maximum short circuit current: 25 mA
Leased line-Output 2
Normal output voltage: 19-28 VDC (open circuit condition)
Supervisory output voltage: -(19-28) VDC (open circuit condition)
Maximum wire resistance: 2-5 k
Maximum short circuit current: 25 mA