NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the
Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be
limited to specific values or not used at all as indicated below.
Program Feature or Option
Settings Permitted in UL 864
Supervision/Trouble Resound
Disable 1 phone line connection
Enable both phone line connections
1 hour, 6 hours and 24 hours
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in
CAN/ULCS527, Standard for Control Units for Fire Alarm Systems, certain programming features or options must be limited to
specific values or not used at all as indicated below.
Program Feature or Option
Settings Permitted in CAN/
ULC-S527
Supervision/Trouble Resound
Disable 1 phone line connection
Enable both phone line connections