70
There is no Ground Fault event in system.
There are ground fault events in system, but
some of them have not been acknowledged.
Alarm
Signal
Activation
(Canada)
The LED 7 can only be steady on when any of
the following conditions are met:
1. There are activated NACs and some of
them are not silenced.
2. There are silenceable devices activated
and some of them are not silenced.
The LED 7 will be OFF when above conditions
are not met.
The buzzer operates as follows:
Normally OFF – indicates that the system is in normal condition or all events in the system
have been acknowledged.
ON (200 pulse per minute) – indicates that at least ONE unacknowledged alarm is present in
the system.
ON (85 pulse per minute) – indicates that at least ONE unacknowledged non-alarm (trouble,
supervisory) event is present in the system.
The buttons operates as follows:
Press button 8 to execute user defined and configured
functions.
Alarm Signal Activation
(Canada)
Press button 8 to report the alarm zone events to the
panel.
The button toggles between silence and unsilence. Press
button 9 to silence the audible and/or visual notification
appliances (where permitted by the codes and control
panel programming). The notification appliances will be
de-activated, and the LED 3 will be off. Press button 9
again to unsilence the previously silenced notification
appliances.
Signal Silence/Unsilence
(Canada)
Acknowledge/Buzzer
Silence
Acknowledges unacknowledged events in system.
Clears all obsolete events and resets all devices, except
those disabled ones and hold-through-reset devices in
system.
Cancel button for PMI operation.
OK button for PMI operation.
* button for PMI operation.
# button for PMI operation.
Numeric buttons for PMI operation. They are used to
enter the password to access the maintenance and
technician modes of the panel. It allows the user to
program the panel using these keypads without using the