GENERAL SPECIFICATIONS
Operating specifications for the FC901 are as follows:
Environmental
Operating temperature - 32 - 120°F (0 - 49°C)
Relative humidity - Up to 93% @ 90°F (32°C)
To be installed in a indoor dry protected environment only
Primary Power Supply
Input: 120VAC, 60Hz or 240VAC, 50Hz
@ 2.0A Max.
Supervised
Output: 26VDC @ 6.5A Max.
Max current: 6.5A (2 hours Max.)
Filtered and Regulated
Secondary Power Supply
24V lead-acid battery set
Max. charged voltage: 27.8VDC
Automatic low battery disconnect voltage: 19.2±0.1VDC
Max. charge current: 0.45A
Battery capacity:12AH to 18AH
Supervised
Auxiliary Power Outputs
Non-resettable power output
Power limited
Alarm status: 0.75A
Normal stand by: 0.05A
Voltage: 19 to 28VDC
Ripple: 0.1VAC
Special Application
Resettable power output
Power limited
Alarm status: 0.75A
Normal stand by: 0.05A
Voltage: 19 to 28VDC
Ripple: 0.1VAC
Special Application
12